EDS-405A-MM-SC
Entry-level managed Ethernet switch with 3 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with SC connectors, 0 to 60°C operating temperature
Ficha de datos
- Industrial Protocols
- EtherNet/IP Modbus TCP
- Management
- Back Pressure Flow Control, BOOTP, DHCP Option 66/67/82, DHCP Server/Client, Flow control, IPv4/IPv6, LLDP, Port Mirror, RARP, RMON, SMTP, SNMP Inform, SNMPv1/v2c/v3, Syslog, Telnet, TFTP
- MIB
- Bridge MIB, Ethernet-like MIB, MIB-II, P-BRIDGE MIB, RMON MIB Groups 1, 2, 3, 9, RSTP MIB
- Time Management
- NTP Server/Client SNTP
- Input Voltage
- 12/24/48 VDC, Redundant dual inputs
- Dimensions
- 53.6 x 135 x 105 mm (2.11 x 5.31 x 4.13 in)
- Peso
- 650 g (1.44 lb)
- Installation
- DIN-rail mounting, Wall mounting (with optional kit)
- Housing
- Metal
- Operating Temperature
- -10 to 60°C (14 to 140°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Freefall
- IEC 60068-2-31
- EMC
- EN 55032/24
- Safety
- UL 508 UL 60950-1
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 20 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6
- Time
- 1,429,327 hrs
- Standards
- IEEE 802.3 for 10BaseT IEEE 802.3u for 100BaseT(X) and 100BaseFX IEEE 802.3x for flow control IEEE 802.1D-2004 for Spanning Tree Protocol IEEE 802.1p for Class of Service IEEE 802.1Q for VLAN Tagging IEEE 802.1w for Rapid Spanning Tree Protocol
Telcordia (Bellcore), GB - Warranty Period
- 5 years
- MAC Table Size
- 2 K
- Packet Buffer Size
- 1 Mbits
- Connection
- 1 removable 6-contact terminal block(s)
- Input Current
- 0.26 A @ 24 VDC
- Operating Voltage
- 9.6 to 60 VDC
- Overload Current Protection
- Supported
- Reverse Polarity Protection
- Supported
- Ethernet Interface
- Turbo Ring, Master, Coupler, Reserve
- IP Rating
- IP30
- Hazardous Locations
- ATEX Class I Division 2
- Maritime
- DNV-GL
- Traffic Control
- NEMA TS2
- Details
- See www.moxa.com/warranty
- Filter
- 802.1Q VLAN, GMRP, GVRP, IGMP v1/v2, Port-based VLAN
- Redundancy Protocols
- RSTP, STP, Turbo Chain, Turbo Ring v1/v2
- IGMP Groups
- 256
- Max. No. of VLANs
- 64
- Priority Queues
- 4
- VLAN ID Range
- VID 1 to 4094
- Console Port
- RS-232 (TxD, RxD, GND), 10-pin RJ45 (19200, n, 8, 1)
- Alarm Contact Channels
- Relay output with current carrying capacity of 1 A @ 24 VDC
No hay ninguna opinión por el momento.